Kinerja teknis
Uji tekanan frekuensi daya basah (luar ruangan) | 54kV,5min |
Tes tekanan frekuensi daya negara garing (ing njero ruangan) | 54kV,5min |
Tes tekanan impact | ± 125kV / 10 kaping |
Tes voltase tahan DC | 96kV / 30 min |
Frekuensi daya tahan test voltase | 48kv 4h |
Tes discharge parsial | ≤10Pc(1.73U₀) |
20kV inti tunggal cold shrinkaksesoris kabeljeneng produk lan model spesifikasi
Jinis lampiran | Spesifikasi kabel (mm²) | Spesifikasi lan model | |
Kabel inti tunggal | Terminal njero ruangan inti tunggal | 35-70 | NSY-20/1.1 |
95-150 | NSY-20/1.2 | ||
185-400 | NSY-20/1.3 | ||
500-630 | NSY-20/1.4 | ||
Terminal njaba inti tunggal | 35-70 | WSY-20/1.1 | |
95-150 | WSY-20/1.2 | ||
185-400 | WSY-20/1.3 | ||
500-630 | WSY-20/1.4 | ||
Konektor intermediate inti tunggal | 35-70 | JSY-20/1.1 | |
95-150 | JSY-20/1.2 | ||
185-400 | JSY-20/1.3 | ||
500-630 | JSY-20/1.4 | ||
Kabel telung inti | Terminal njero ruangan telung inti | 35-70 | NSY-20/3.1 |
95-150 | NSY-20/3.2 | ||
185-400 | NSY-20/3.3 | ||
500-630 | NSY-20/3.4 | ||
Terminal ruangan telung inti | 35-70 | WSY-20/3.1 | |
95-150 | WSY-20/3.2 | ||
185-400 | WSY-20/3.3 | ||
500-630 | WSY-20/3.4 | ||
Konektor tengah telung inti | 35-70 | JSY-20/3.1 | |
95-150 | JSY-20/3.2 | ||
185-400 | JSY-20/3.3 | ||
500-630 | JSY-20/3.4 |