BY1-C40/1P | | 75 | 150 | 275 | 320 | 385 | 440 |
IEC listrik | | | | | | | |
Tegangan AC Nominal (50/60Hz) | U0/Un | 60V | 120V | 230V | 230V | 230V | 400V |
Tegangan Operasi Kontinu Maksimum (AC) | UC | 75V | 150V | 275V | 320V | 385V | 440V |
Nominal Discharge Saiki (8/20μs) | In | 20KA | 20KA | 20KA | 20KA | 20KA | 20KA |
Arus Discharge Maksimum (8/20μs) | Imaks | 40KA | 40KA | 40KA | 40KA | 40KA | 40KA |
Tingkat Proteksi Tegangan | Up | 40V | 1000V | 1500V | 1600V | 1750V | 2000V |
Wektu Respon | tA | <25ns |
Sekring serep (maks) | | 125A gL/gG |
Peringkat Arus Sirkuit Pendek (AC) | ISCCR | 25KA/50KA |
TOV Tahan 5s | UT | 90V | 180V | 335V | 335V | 335V | 580V |
UT | 115V | 230V | 440V | 440V | 440V | 765V |
TOV 120 min | modus | Tahan | Tahan | Gagal Aman | Gagal Aman | Gagal Aman | Gagal Aman |
Jumlah Pelabuhan | | 1 |
UL listrik | | | | | | | |
Tegangan Operasi Kontinu Maksimum (AC) | MCOV | 75V | 150V | 275V | 320V | 385V | 440V |
Rating Proteksi Tegangan | VPR | 330V | 600V | 900V | 1000V | 1200V | 1500V |
Nominal Discharge Arus (8/20μs) | In | 20KA | 20KA | 20KA | 20KA | 20KA | 20KA |
Peringkat Arus Sirkuit Pendek (AC) | SCCR | 100KA | 200KA | 150KA | 150KA | 150KA | 200KA |