Parameter utama | | unit | NQ-40 |
Rated voltase insulasi | Ui | V | 1500 |
Rated saiki termal | Ith | A | 32 |
Rated impuls tahan voltase | Uimp | V | 8000 |
Kapasitas nggawe sirkuit cendhak sing dirating | lcw | A | 1000 |
Bagian silang kabel maksimal (kalebu jumper) | | |
Solid utawa standar | mm² | 2.5-6 |
Fleksibel | mm² | 2.5-6 |
Fleksibel (+ ujung kabel multicore) | mm² | 2.5-6 |
Torsi | | |
Ngencangake sekrup terminal torsi M4. | Nm | 1.2-1.8 |
Ngencengi sekrup pemasangan cangkang torsi | Nm | 1.5-2.0 |
Ngencengi sekrup torsi | Nm | 0.5-0.7 |
Ngaktifake utawa mateni Torsi | Nm | 0.9-1.3 |
Torsi kabel ing Base | Nm | 1.1-1.4 |
Paramèter umum | | |
Posisi tombol | | OFF jam 9, ON jam 12 |
urip mekanik | | 10000 |
Jumlah kutub DC | | 2 utawa 4 |
Suhu operasi | | -40 nganti +85 |
Suhu panyimpenan | | -40 nganti +85 |
Gelar polusi | ℃ | 2 |
Kategori overvoltage | ℃ | Ⅲ |
Rating IP saka shafte lan soyo tambah nul | | IP66 |