Tipe VS ditrapake kanggo baris AC 230V ing kutub siji, 400V ing pindho, telu, papat kutub kanggo nglindhungi kakehan lan sirkuit cendhak, lan dirating saiki nganti 63A. Sampeyan uga bisa digunakake kanggo konversi baris arang ing kondisi normal. IEC60898.
Jinis | VS | |||
Pole | 1P | 2P, 3P.4P | ||
Rated saiki (A) | 6.10,16,20,25,32,40,50,63 | |||
Tegangan Rated (V) | 230 | 400 | ||
Suhu sekitar | -5 ℃ ~ + 40 ℃ | |||
Jinis release cepet | B,C | D | B,C | D |
Kapasitas putus hubung singkat Icn(kA) | 1-32A:6 | 4.5 | 1-32A:6 | 4.5 |
50-63A:4.5 | 50-63A:4.5 |
Jinis | Potongan silang normal kawat mm² |
1-6A | 1 |
10A | 1.5 |
16,20A | 2.5 |
25A | 4 |
32A | 6 |
40,50A 63A | 10 16 |
Suhu Sekitar | Awal S tatus | TestSaiki | Hasil sing Dikarepake | Hasil sing Dikarepake | Cathetan |
30+2 ℃ | Posisi kadhemen | 1.13ln | t1h | Non-release | |
Digawa metu langsung sawise | 1.45 Ing | t<1h | Ngeculake | ||
Posisi kadhemen | 2.55 Ing | 1s | Ngeculake | Saiki mundhak lancar menyang nilai sing ditemtokake sajrone 5 detik | |
Posisi kadhemen | 2.55 Ing | 1s | Ngeculake | ||
-5 ~ + 40 ℃ | Posisi kadhemen | 3ln | t0.1s | Non-release | Tipe B |
Posisi kadhemen | 5 Ing | t<0.1s | Ngeculake | Tipe B | |
Posisi kadhemen | 5 Ing | t0.1s | Non-release | TipeC | |
Posisi kadhemen | 10ln | t<0.1s | Ngeculake | Tipe C | |
Posisi kadhemen | 10ln | t0.1s | Non-release | Tipe D | |
Posisi kadhemen | 20ln | t<0.1s | Ngeculake | Tipe D |