Spesifikasi
Saben kutub konsumsi daya mbobol sirkuit
| listrik Fitur | Standar |
| IEC/EN 60898-1 |
| Rated saiki Ing | A | 1,2,4,6,10,16,20,25,32,40,50,63 | |
| Kutub | P | 1,2,3,4 | |
| Tegangan Rated Ue | V | AC 240/415 | |
| Tegangan isolasi Ui | V | 500 | |
| frekuensi dirating | Hz | 50/60 | |
| Kapasitas rusak sing dirating | A | 3000,4500(2~40A/6000) | |
| Impuls sing dirating kanthi tegangan ngadeg (1.2/50) Uimp | V | 4000 | |
| Tegangan uji dielektrik ing ind. Frqu, kanggo 1 min | KV | 2 | |
| Gelar polusi |
| 2 | |
| Karakteristik release termo-magnetik |
| B, C, D | |
| urip listrik | T | 4000 | |
| urip mekanik | T | 10000 | |
| Gelar pangayoman |
| IP20 | |
| Suhu referensi kanggo | ℃ | 30 | |
| Setelan unsur termal |
| ||
| Suhu sekitar (kanthi rata-rata saben dina≤35℃) | ℃ | -5 ~ + 40 (Aplikasi khusus mangga deleng koreksi kompensasi suhu) | |
| Suhu panyimpenan | ℃ | -25~+70 | |
| Instalasi | Tipe sambungan terminal |
| Kabel / Pin jinis busbar / U jinis busbar |
| Ukuran terminal ndhuwur / ngisor kanggo kabel | mm2 | 25 | |
| AWG | 18-3 | ||
| Ukuran terminal ndhuwur / ngisor kanggo busbar | mm2 | 25 | |
| AWG | 18-3 | ||
| N*m | 2 | ||
| Ing-Ibs. | 18 | ||
| Pemasangan |
| ||
| Sambungan |
|
Penurunan suhu
Mangga deleng tabel ing ngisor iki kanggo koreksi kompensasi suhu
| Dirating Saiki Ing (A) | Koefisien kompensasi suhu ing macem-macem suhu operasi | ||||||||
| -10℃ | 0℃ | 10℃ | 20℃ | 30℃ | 40℃ | 50℃ | 55℃ | 60℃ | |
| 1-6 | 1.20 | 1.14 | 1.09 | 1.05 | 1.00 | 0.96 | 0.80 | 0.75 | 0.70 |
| 10-32 | 1.18 | 1.12 | 1.08 | 1.04 | 1.00 | 0.96 | 0.92 | 0.88 | 0.84 |
| 40-60 | 1.16 | 1.12 | 1.07 | 1.03 | 1.00 | 0.97 | 0.87 | 0.83 | 0.80 |