Teknologi Khusus Kompresor UdaraParameter Lan Mode (WQC)
| Tipe | Kekuwatan | Tegangan | Arus sing dirating | Cakupan sing wis diatur kanggo bagean relay termal |
| WQC-12 | 0.75KW | 380V | 2.1A | 1.7-2.5A |
| WQC-12 | 1.1KW | 380V | 2.5A | 2-3A |
| WQC-12 | 1.5KW | 380V | 3.6A | 2.8-4.4A |
| WQC-12 | 2.2KW | 380V | 5A | 4-6A |
| WQC-12 | 3KW | 380V | 6.6A | 5.2-8A |
| WQC-32 | 4KW | 380V | 9A | 7-11A |
| WQC-32 | 5.5KW | 380V | 11A | 9-13A |
| WQC-32 | 7.5KW | 380V | 15A | 12-18A |
| WQC-32 | 11KW | 380V | 22A | 20-32A |
| WQC-50 | 15KW | 380V | 30A | 28-45A |
| WQC-50 | 18.5KW | 380V | 37A | 40-63A |
| WQC-65 | 18.5KW | 380V | 37A | 40-63A |
| WQC-85 | 22KW | 380V | 44A | 40-63A |
| WQC-95 | 30KW | 380V | 60A | 53-85A |
| Tipe | Kontaktor | Relay termal standar | Daya motor kontrol (KW) | Arus sing dirating (A) | ||||
| Tipe | Arus sing wis disetel | 220V | 380V | 500V | 220V | 380V | ||
| QCX5-9 | CJX5-9 | JRS-5-12/Z | 3.6A | 0.75 | 1.5 | 2.2 | 11 | 9 |
| QCX5-9 | CJX5-9 | JRS-5-12/Z | 5A | 1.1 | 2.2 | 3 | 11 | 9 |
| QCX5-9 | CJX5-9 | JRS-5-12/Z | 6.6A | 1.5 | 3 | 3.7 | 11 | 9 |
| QCX5-9 | CJX5-9 | JRS-5-12/Z | 9A | 2.2 | 4 | 5.5 | 11 | 9 |
| QCX5-12 | CJX5-12 | JRS-5-12/Z | 3.6A | 0.75 | 1.5 | 2.2 | 13 | 12 |
| QCX5-12 | CJX5-12 | JRS-5-12/Z | 5A | 1.1 | 2.2 | 3 | 13 | 12 |
| QCX5-12 | CJX5-12 | JRS-5-12/Z | 6.6A | 1.5 | 3 | 3.7 | 13 | 12 |
| QCX5-12 | CJX5-12 | JRS-5-12/Z | 9A | 2.2 | 4 | 5.5 | 13 | 12 |
| QCX5-12 | CJX5-12 | JRS-5-12/Z | 11A | 3 | 5.5 | 7.5 | 13 | 12 |
| QCX5-22/11 | CJX5-22/11 | JRS-5-20/F | 11A | 3 | 5.5 | 7.5 | 22 | 22 |
| QCX5-22/11 | CJX5-22/11 | JRS-5-20/F | 15A | 3.7 | 7.5 | 9 | 22 | 22 |
| QCX5-22/22 | CJX5-22/22 | JRS-5-20/F | 11A | 3 | 5.5 | 7.5 | 22 | 22 |
| QCX5-22/22 | CJX5-22/22 | JRS-5-20/F | 15A | 3.7 | 7.5 | 9 | 22 | 22 |
| QCX5-32 | CJX5-32 | JRS-5-20/F | 19A | 5.5 | 11 | 11 | 30 | 30 |
| QCX5-32 | CJX5-32 | JRS-5-20/F | 22A | 5.5 | 11 | 11 | 30 | 30 |
| QCX5-40 | CJX5-40 | JRS-5-20/F | 19A | 5.5 | 11 | 11 | 40 | 40 |
| QCX5-40 | CJX5-40 | JRS-5-20/F | 22A | 5.5 | 11 | 11 | 40 | 40 |
| QCX5-40 | CJX5-40 | JRS-5-20/F | 29A | 7.5 | 15 | 18.5 | 40 | 40 |
| QCX5-40 | CJX5-40 | JRS-5-20/F | 35A | 9 | 18.5 | 22 | 40 | 40 |
Dimensi lan Pemasangan Dimensi
■ Starter bisa digunakake sajrone wektu sing suwe lan tanpa relay termal sing bisa digunakake. Frekuensine bisa 600 kali/jam sajrone wektu sing cendhak lan bisa digunakake bola-bali;
■ Koil tarikan bisa berfungsi kanthi andal nalika voltase terukur 85% ~ 105%, voltase sing dirilis kira-kira voltase terukur 40 ~ 55%;
■ Kontak starter ing frekuensi operasi yaiku 600/jam, telegram bunder terus mimpin kanggo merit 40%. Nempatake liwat arus nominal sing dilebokake, nalika pamisahan faktor kasebut 0,35, Umur listrik ora luwih murah tinimbang 640.000 kali;
■ Umur mekanik starter iku 3 yuta kali lipat;
■ Kontak bantu starter, arus nominale 5A;
■ Relay termal nduweni organisasi kompensasi suhu, Bisa nyeimbangake suhu sing disebabake dening owah-owahan voltase suhu sekitar;
■ Overload relay termal ana ing syarat-syarate. Kanggo ndeleng ing ngisor iki.